Roof sarking: when the NCC needs it, and how many rolls.

Tiled and metal roofs, by NCC Parts 7.3 and 10.8. It works in your browser; nothing you enter is sent anywhere.

Sarking

Roof along the slope
Each roll covers, lapped
With waste
Rolls cost
Sarking under the NCC
Anti-ponding board

What sarking does

Sarking is a flexible membrane laid over the rafters or trusses, under the battens. Under tiles it catches the rain and dust that wind drives between them and runs it down to the gutter. Foil-faced sarking also counts as reflective insulation when it faces an air gap of at least 20 mm. In the NCC and the makers’ data sheets it’s a “pliable building membrane” or “sarking-type material”, made to AS/NZS 4200.1.

When a tiled roof needs sarking

NCC Housing Provisions 7.3.4 sets it by pitch and by rafter length, measured down the rafter or truss top chord from the apex; use the longest one. Past the length in the table, the rest of the rafter down to the eaves has to be sarked. The table is the same in NCC 2022 and NCC 2025.

Roof pitchLongest rafter without sarking
Under 18°None: sark the whole roof
18° to under 20°4,500 mm
20° to under 22°5,500 mm
22° and steeper6,000 mm
Table 7.3.4, Sarking requirements for tiled roofs.

Where sarking goes in, 7.3.4 also says how:

  • Made to AS 4200.1.
  • Each sheet or roll lapped at least 150 mm over the next, or taped together.
  • Fixed at no more than 300 mm centres to the rafters or trusses.
  • No sag deeper than 40 mm.

Then 7.3.5: wherever sarking goes on a tiled roof under 20°, or on a roof with no eaves overhang at any pitch, it needs an anti-ponding board. It’s water resistant, fixed along the eaves from the top of the fascia back up the rafter, about 50 mm below the first batten, so water on the sarking can’t pool behind the fascia.

Part 7.3 only covers tiled roofs from 15° to 35°, in wind class N3 or lower, with tiles to AS 2049. Anything else is built to AS 2050 (NCC Volume Two, H1D7).

Under a metal roof

NCC Part 7.2, for metal sheet roofs, has no sarking rule. It’s still common under metal: Fletcher’s data sheet for its metal-roof sarking sells it on cutting rain noise and draughts. The rule that does reach metal roofs is condensation, in Part 10.8.

Condensation: climate zones 6, 7 and 8

Part 10.8 only applies in NCC climate zones 6, 7 and 8, the cooler parts of Australia. Look up an address on the ABCB climate map; the ABCB says not to go by postcode or council area, because zone lines cross them. Which version applies depends on the state:

  • NSW and Tasmania keep NCC 2022’s Part 10.8, even under NCC 2025. The roof needs a space at least 20 mm high above the insulation, ventilated to outside air through openings spread evenly (Table 10.8.3), unless it sits right under the tiles of an unsarked tiled roof. If sarking is laid straight onto the insulation, the space can go above the sarking instead, but only if the sarking has a vapour permeance of at least 1.14 μg/N.s.
  • Other states, once they adopt NCC 2025 (from 1 May 2026, each on its own date): the roof space above the insulation is at least 18 mm high and ventilated, with the openings in Table 10.8.3 (for pitches from 10° to under 75°, 7,000 mm² a metre at the eaves and 5,000 mm² a metre up high). Where the insulation runs parallel to the roof, a sarking or other control layer laid straight on it needs a vapour permeance of at least 1.14 μg/N.s. A tiled roof with no control layer above the insulation is exempt.

In both versions, concrete roofs, insulated panel roofs and roofs built to BAL-FZ are exempt.

Why it matters for the sarking you buy: ordinary foil sarking stops vapour. Fletcher’s data sheet for its foil tile-roof sarking lists it as a Class 1 vapour barrier. Laid straight onto a blanket under a metal roof in these zones, you want a vapour-permeable sarking instead. Fletcher’s Vapawrap metal-roof membrane lists a permeance above 1.1403 μg/N.s (Class 4), and Bradford sells Enviroseal Tuff as a vapour-permeable roof underlay. Check the figure on the data sheet of whatever you use.

Bushfire-prone areas

On a bushfire-prone block, the roof is built to AS 3959 for its Bushfire Attack Level (BAL). The standard is paywalled, so read your BAL report and the roofing and sarking makers’ guides. CSR Bradford’s summary: from BAL-12.5 to BAL-40, low-flammability sarking is mandatory, and BAL-FZ needs more on top. Makers test the flammability index to AS 1530.2 and print it on the data sheet; Fletcher’s tile and metal roof sarking both list 5 or less.

How the calculator counts rolls

  1. A plan area (eaves included) becomes the area along the slope: plan area ÷ cos(pitch). The roof pitch calculator gives the same factor.
  2. Each roll covers its width less the lap, times its length, because the next run up overlaps it.
  3. It adds your waste for hips, valleys, end laps and offcuts, and rounds up to whole rolls.

The 5% waste is a starting figure, not a rule: a plain gable wastes less, a roof full of hips and valleys more. The NCC’s 150 mm lap is for tiled roofs; use the maker’s lap under metal sheets.

A worked example

A tiled roof at 20°, 150 m² on plan, with a 6.2 m rafter from apex to eaves:

  • At 20° the rafter can run 5,500 mm without sarking, so the NCC needs the lowest 700 mm of each rafter sarked. At 20° with eaves, no anti-ponding board.
  • Sarking the whole roof is simpler, and the calculator counts it that way. Along the slope that’s 150 ÷ cos 20° = 159.6 m², or 167.6 m² with 5% waste.
  • A 1500 mm × 30 m roll lapped 150 mm covers 1.35 × 30 = 40.5 m², so that’s 5 rolls.

Roll sizes

RollAreaLapped 150 mmFor example
1350 mm × 30 m40.5 m²36 m²Fletcher Sisalation Metal Roof MD, Sisalation Vapawrap metal roof
1350 mm × 60 m81 m²72 m²Fletcher Sisalation Metal Roof MD and HD
1500 mm × 30 m45 m²40.5 m²Fletcher Sisalation Tile Roof, Bradford Enviroseal Tuff
From the makers’ data sheets, checked 2 November 2026. Ask your supplier what they stock.

From roof to price

We don’t publish sarking prices: they change by supplier and by brand. Put your own price a roll into the calculator. On a full quote, that’s the job Deftara Quoting does for roofers: sarking, sheets and flashings from your own price list, each priced as your cost plus your markup.

More for trades

Sources

Talk to us

Quoting roofs?

Deftara Quoting prices sarking, sheets and flashings from your own supplier list. Tell us how you quote now.

We need your name and an email or a phone number. The rest helps us prepare.

We only use these details to reply to you. Privacy

What happens next

  1. Talk

    Tell us how the business runs and what you use now.

  2. Match

    We pick the closest app and tell you what would change.

  3. Set up

    Your branding, your data and your team’s logins, at no cost.

  4. Go live

    Your team starts using it on its own copy.

Prefer email? Send a recent quote to hello@deftara.com.au, with the prices blanked out if you like.